<15. OS Function Block>

15-1

IM 21B04C01-01E

15. OS Function Block

15.1 General

The OS (output splitter) function block is used

to split a single control signal into two parts for

coordinating the actions of two or more valves, such

as for split-range control or sequencing control of

a large and a small valves. The OS block receives

a control signal and converts it into two signals in

accordance with the predefined relationships. The

major functions of the OS block include:

• Conversion of the setpoint (SP) value into

two output values (OUT_1 and OUT_2)

in accordance with the user-specified

characteristics (set in IN_ARRAY and OUT_

ARRAY)

• Generation of the output value to be fed back to

the upstream block (BKCAL_OUT)

F1501.ai

OS

CAS_IN

BKCAL_IN_1
BKCAL_IN_2

BKCAL_OUT
OUT_1
OUT_2

Figure 15.1 Inputs/Outputs of OS Function Block

F1502.ai

Output

X21, X22

Y21, Y22

BKCAL_IN_1

Cas

Auto

SP

BKCAL_OUT

OUT_1

CAS_IN

OUT_2

BKCAL_IN_2

Output

X11, X12

Y11, Y12

LOCKVAL

Figure 15.2 Function Diagram of OS Function

Block

15.2 Modes

The target mode for the OS function block can

be set from three block modes: Cas, Auto, and

O/S. Regardless of the target mode, the OS

block automatically enters the IMan mode when a

specified condition is met.

15.3 Output Processing

The values of OUT_1 and OUT_2 with respect to

the value of SP, which is the value of the input from

the upstream block (CAS_IN) in the Cas mode

or the local setpoint value in the Auto mode, are

determined as shown in the following graphs.

F1503.ai

Split-range Control

Valve Sequencing Control

100%

50%

0%

P1

(X11, Y11)

OUT_1 OUT_2

P3

(X21, Y21)

P2

(X12, Y12)

P4

(X22, Y22)

0%

50%

100%

SP

100%

50%

0%

P1

(X11, Y11)

OUT_1

OUT_2

P4

(X22, Y22)

P2

(X12, Y12)

P3

(X21, Y21)

0%

50%

100%

SP

OUT

OUT

Figure 15.3 Examples of Valve Operation

Characteristics

These characteristics are determined by the array

element values in parameters IN_ARRAY and

OUT_ARRAY.

IN_ARRAY: [X11, X12, X21, X22]

OUT_ARRAY: [Y11, Y12, Y21, Y22]

Coordinates P1 (X11, Y11) and P2 (X12, Y12)

define the start and stop points of the characteristics

for OUT_1, and P3 (X21, Y21) and P4 (X22, Y22)

define those for OUT_2. These two operation

characteristics may overlap each other, or start from

the same point and have different slopes; however,

all the following conditions must be met at all times.

Settings of IN_ARRAY that do not meet one or

more of these conditions cause a BLOCK_ERR,

disabling the block from exiting the O/S mode.

X21 ≥ X11

X12 > X11

X22 > X21

In areas outside the endpoints (i.e., start and stop

points) of each operation characteristic, the output

is retained at the Y value at the nearer end point.

For OUT_1, however, depending on the setting of

LOCKVAL, it is possible to:

Set the value of OUT_1 to Y11 in the areas

outside the endpoints if SP is greater than X12

and if LOCKVAL is false.