<1. Notes on Handling>

1-5

IM 21B04C01-01E

SAFE AREA

HAZARDOUS AREA

F0103.ai

Terminator

(FISCO Model)

Ex i

Field Instruments

(Passive)

Supply Unit

(FISCO Model)

Terminator

Data

U

U

I

Note 5. Maintenance and Repair

The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void Factory

Mutual Intrinsically Safe and Non-incendive

Approval.

l

Installation Diagram (Nonincendive,

Division 2 Installation)

F0104.ai

Terminator

Valve Positioner

Terminator

+

Transmitter

+

Transmitter

+

Hazardous Location

Non-hazardous Location

FM Approved Associated

Nonincendive Field Wiring Apparatus

Vt or Voc

It or Isc

Ca

La

(Nonincendive)

Power Supply

*1: Dust-tight conduit seal must be used when

installed in Class II and Class III environments.

*2: Installation should be in accordance with the

National Electrical Code® (ANSI/NFPA 70)

Sections 504 and 505.

*3: The configuration of Associated Nonincendive

Field Wiring Apparatus must be FM Approved.

*4: Associated Nonincendive Field Wiring

Apparatus manufacturer’s installation

drawing must be followed when installing this

equipment.

*5: No revision to drawing without prior FM

Approvals.

*6: Terminator and supply unit must be FM

Approved.

*7: If use ordinary wirings, the general purpose

equipment must have nonincendive field wiring

terminal approved by FM Approvals.

*8: The nonincendive field wiring circuit concept

allows interconection of nonincendive field

wiring apparatus with associated nonincendive

field wiring apparatus, using any of the wiring

methods permitted for unclassified locations.

*9: Installation requirements;

Vmax ≥ Voc or Vt

Imax = see note 10.

Ca ≥ Ci + Ccable

La ≥ Li + Lcable

*10: For this current controlled circuit, the parameter

(Imax) is not required and need not be aligned

with parameter (Isc or It) of the barrier or

associated nonincendive field wiring apparatus.

Electrical Data:

Maximum Input Voltage Vmax: 32 V

Maximum Internal Capacitance Ci: 1.76 nF

Maximum Internal Inductance Li: 0 µH

B) FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model YVP110 Valve Positioner with

optional code /FF1 are applicable for use in

hazardous locations.

• Applicable standard: FM3600, FM3615,

FM3810, ANSI/NEMA250

• Explosionproof for Class I, Division 1,

Groups A, B, C and D

• Dust-ignitionproof for Class II/III, Division 1,

Groups E, F and G

• Enclosure Rating: NEMA 4X

• Temperature Class: T6

• Ambient Temperature: –40 to 80°C