17 alarms, 1 block alarm (block_alm), 2 process alarms – Yokogawa YVP110 User Manual

Page 86: 17 alarms -5

Advertising
background image

<16. PID Function Block>

16-5

IM 21B04C01-01E

Table 16.5

SHED_OPT of PID Block

Available

Setting for

SHED_OPT

Actions upon Computer Failure

Normal shed,

normal return

Sets MODE_BLK.actual to Cas*

1

,

and leaves MODE_BLK.target

unchanged.

Normal shed, no

return

Sets both MODE_BLK.actual and

MODE_BLK.target to Cas*

1

.

Shed to Auto,

normal return

Sets MODE_BLK.actual to Auto*

2

,

and leaves MODE_BLK.target

unchanged.

Shed to Auto, no

return

Sets both MODE_BLK.actual and

MODE_BLK.target to Auto*

2

.

Shed to Manual,

normal return

Sets MODE_BLK.actual to Man,

and leaves MODE_BLK.target

unchanged.

Shed to Manual,

no return

Sets both MODE_BLK.actual and

MODE_BLK.target to Man.

Shed to retained

target, normal

return

If Cas is set in MODE_BLK.target,

- sets MODE_BLK.actual to Cas*

1

and

- leaves MODE_BLK.target

unchanged.

If Cas is not set in MODE_BLK.

target,

- sets MODE_BLK.actual to Auto*

2

and

- leaves MODE_BLK.target

unchanged.

Shed to retained

target, no return

If Cas is set in MODE_BLK.target,

sets:

- MODE_BLK.actual to Cas, and

- MODE_BLK.target to Cas*

1

, too.

If Cas is not set in MODE_BLK.

target, sets:

- MODE_BLK.actual to Auto*

2

, and

- MODE_BLK.target to Cas.

*1:

The modes to which the PID block can transfer are limited

to those set in MODE_BLK.permitted, and the priority

levels of modes are as shown below. In fact, if Normal

shed, normal return is set for SHED_OPT, detection of a

computer failure causes MODE_BLK.actual to change

to Cas, Auto, or Man, whichever is set in MODE_BLK.

permitted and has the lowest priority level.

Man

Auto

Cas

RCas

ROut

Higher priority level

Lower priority level

*2:

Only when Auto is set as permitted mode.

NOTE: If a control block is connected as a cascade

primary block of the PID block in question, a mode

transition of the PID block to Cas occurs in the following

sequence due to initialization of the cascade connection:

RCas or ROut → Auto → Cas.

16.17 Alarms

There are two kinds of alarms generated by a PID

block: block and process alarms.

16.17.1 Block Alarm (BLOCK_ALM)

The block alarm BLOCK_ALM is generated upon

occurrence of either of the following errors (values

set in BLOCK_ERR) and notifies the content of

BLOCK_ERR.

Bit

Value of

BLOCK_ERR

Condition

4 Local Override MODE_BLK.actual of the PID

block is LO.

7 Input Failure

The status of PV is Bad.

(The status of IN is Bad, or the

status of IN is Uncertain and

“Use Uncertain as Good” is false

in STATUS_OPTS).

15 Out of Service

MODE_BLK.target of the PID

block is O/S.

16.17.2 Process Alarms

There are six types of process alarms. Only one

process alarm can be generated at a time, and

the process alarm having the highest priority level

from among those occurring at the same time is

generated. The priority level is set for each process

alarm type.

Process

Alarm

Cause of Occurrence

Parameter

Containing

Priority

Level

Setting

HI_HI_ALM

Occurs when the PV

increases above the

HI_HI_LIM value.

HI_HI_PRI

HI_ALM

Occurs when the PV

increases above HI_LIM

value.

HI_PRI

LO_ALM

Occurs when the PV

decreases below the

LO_LIM value.

LO_PRI

LO_LO_ALM Occurs when the PV

decreases below the

LO_LO_LIM value.

LO_LO_LIM

DV_HI_ALM Occurs when the value

of [PV -SP] increases

above the DV_HI_LIM

value.

DV_HI_PRI

DV_LO_ALM Occurs when the value

of [PV -SP] decreases

below the DV_LO_LIM

value.

DV_LO_PRI

Advertising