<Appendix 1. Function Block Parameters>

A-17

IM 21B04C01-01E

Relative

Index Index

Parameter

Name

Valid

Range

Default

(factory

setting)

Write

Description

14

17514 IN

0

Input block

15

17515 IN_LO

0

Input for a low-range transmitter.

This is used for the range extension function.

16

17516 IN_1

0

Auxiliary input 1

17

17517 IN_2

0

Auxiliary input 2

18

17518 IN_3

0

Auxiliary input 3

19

17519 RANGE_HI

0

High limit for switching to a high-range transmitter by the

range extension function.

20

17520 RANGE_LO

0

Low limit for switching to a low-range transmitter by the

range extension function.

21

17521 BIAS_IN_1

0

IN_1 bias

22

17522 GAIN_IN_1

0

IN_1 gain

23

17523 BIAS_IN_2

0

IN_2 bias

24

17524 GAIN_IN_2

0

IN_2 gain

25

17525 BIAS_IN_3

0

IN_3 bias

26

17526 GAIN_IN_3

0

IN_3 gain

27

17527 COMP_HI_

LIM

+INF

High limit of compensation factor f

28

17528 COMP_LO_

LIM

-INF

Low limit of compensation factor f

29

17529 ARITH_

TYPE

1 to 10

0x01

Computation algorithm identification number.

Value

Selection Name

Description

1

Flow compensation,

linear

Flow compensation

(linear)

2

Flow compensation,

square root

Flow compensation

(square root)

3

Flow compensation,

approximate

Flow compensation

(approximate

expression)

4

BTU flow (*)

Quantity of heat

calculation

5

Traditional Multiply

Divide

Multiplication and

division

6

Average

Average calculation

7

Traditional summer

Summation

8

Fourth order

Polynomial, Type 1

4th-order (auxiliary

input) polynomial

computation

9

HTG level

compensation (*)

HTG level

compensation

10

Fourth order

Polynomial ,Type 2

4th-order (main

input) polynomial

computation

* BTU stand for British thermal value

HTG stands for hydrostatic tank gauging

30

17530 BAL_TIME More than

0

0

Time taken to return to the set value

31

17531 BIAS

0

Bias value used to calculate the output

32

17532 GAIN

1

Gain value used to calculate the output

33

17533 OUT_HI_

LIM

+INF

Maximum output value

34

17534 OUT_LO_

LIM

-INF

Minimum output value

35

17535 UPDATE_

EVT

Indicate event information if an update (setting change)

occurs.

36

17536 BLOCK_

ALM

Indicates alarm information if a block alarm occurs.