4.32 Sending Setting Data

Send the DARWIN Hardware configurator setting data to the DA100/DR/DC100 as
follows.

1

Select from the menubar Comm. > Send > and then, All Settings, SET (Regular)
Settings Only, or Modified CH/Math Settings.

Depending on which settings you want to send to the DARWIN hardware, and

possibly to save a lot of sending time, select:

• All Settings.

• SET (Regular) Settings Only.
• Modified CH/Math Settings. This means sending all the settings actually

modified on the Channels and Math setting screens only.

2

Sending will start after you click OK when the reconfirmation message is

displayed.

Note

• Before connecting the hardware, check if Module Configuration matches the actual module

construction.

• If a file remains in the internal RAM disk of the DC100, it is not possible to send settings

to its internal RAM disk. Initialize the internal DC100 RAM disk before sending data to the

DC100, or initialize the DC100 using this software. In that case, make sure to first copy

important files.

• If files remain on the DC100 internal RAM disk, when sending data to the DC100 the writing

action does not change automatically to SINGLE or REPEAT, when it was earlier set to

NONE on the DC100, and likewise, not to NONE if it is set to SINGLE or REPEAT on the

DC100.

• If files remain on the DC100 internal RAM disk, when sending data to the DC100 , the

periodic file type (see Section 4.18) does not change automatically to Meas or Report, when

it was earlier set to NONE on the DC100, and likewise, not to NONE if it is set to Meas or

Report on the DC100.

• If the following settings have been changed, only the channel data for the SET (regular)

mode will be send.

• System configuration, or module construction.

• Initialization of edited data.

• Re-configuration.

• Initialization of DA100, DC100, DR.

• Writing method of measurement data.

• Communication is not possible of the Logging monitor or record function is active.

• If data are send, during computation, reporting, or (for DC only) data writing, those actions

will be canceled.

• If only altered settings are send event/action, Math, Report, or Memory Pause, LEVEL

actions, will not be canceled.

• When using ether communication, error detection may take a few minutes.