Reflash alarm

In general, in cases where one alarm output relay is shared by more than two channels,

no alarm signal will be issued if an alarm occurs in another channel or at another alarm

level, once an alarm has occurred in one channel and the alarm signal has been issued.

In this case, the alarm signal can be issued by designating the reflash output relay

(designated by alarm setting) as the alarm output relay. Up to six relays can be

designated as reflash relays.

Alarm state

Alarm output

relay

Channel 1

Channel 3

Channel 2

Output relay

Approx.

500 ms

Approx.

500 ms

Reflash alarm ON

Alarm output

relay

Reflash alarm OFF

Output relay

(A reflash relay is designated as

the output relay)
(A reflash relay is designated as

the output relay)

(A reflash relay is designated as

the output relay)

(Reflash relay output)

(Reflash relay output)

Alarm output relay hold/non-hold

Each alarm output relay can be switched to the hold mode or non-hold mode.

However, non-hold always applies to relays for which the reflash alarm is set, regardless
of the hold/non-hold setting.

Non-hold mode:

Each alarm output relay is activated according to its alarm ON/OFF state.

Alarm ON

Alarm OFF

Output relay ON

Output relay OFF

Hold mode:

Once an alarm occurs, the alarm output relay continues to be activated even if the alarm

is turned OFF. To stop the alarm relay output, reset the alarm using a communication
command. For a description of communications commands, see the GP-IB/RS232-C
Interface User’s Guide.

Alarm ON

Alarm OFF

Output relay ON

Output relay OFF

Alarm reset