Index

Before Operation

Alarm output relay energize/de-energize

The alarm output relay can be switched between energizing mode and de-energizing

mode. If de-energizing mode is selected, the alarm relay can still be energized in the

same way as when an alarm occurs, even if the power is turned OFF due to a power

failure or other reasons.

NO

energizing

mode

de-

energizing

mode

C

NC

NO

C

NC

NO

C

NC

NO

C

NC

NO

C

NC

NO

C

NC

Power is OFF

Alarm is present

No alarm is present

NO

energizing

mode

de-

energizing

mode

C

NO

C

NO

C

NO

C

NO

C

NO

C

Power is OFF

Alarm is present

No alarm is present

a-contact

c-contact

Alarm output relay AND/OR

If one alarm output relay is shared by more than two channels or alarm levels, the output

method for the alarm output relay can be selected from the following two methods.

AND : Energizes the alarm relay when all the alarms occur simultaneously.

OR : Energizes the alarm relay when an alarm occurs in any of the channels or at any

of the alarm levels.

Alarm

Channel 1

AND

Channel 2

OR

Alarm output relay

Note

The reflash relay is always used in OR mode.