Error Messages <Software Configuration>

No.

Message/Corrective action

E3301

Failed to scan.
Check that the DARWIN is turned ON, the communication module is being recognized by the DARWIN (DR/
DC), and the cable is connected properly.

In addition, check the following items according to the communication methods.

For GPIB communication:

Is the address correct? Is the driver is properly installed? Is the GPIB card manufactured by NI?

For Ether communication:
Is the address correct? Is the TCP/IP protocol installed in Windows? Is the Ether card properly installed?
For RS-232-C, RS-422-A, and RS-485

Is the baud rate correct? Is the port (COM1 to COM4) correct? Is the address correct (RS422)? Is the PC’s
serial port functioning? Is the correct type of cable being used?

E3302

Failed to reconstruct.

See the corrective actions for E3301.

E3303

Failed to initialize.

See the corrective actions for E3301.

E3306

Fail to make directory.

Check the directory path and name.

E3312

Select all ranges that has invalid values.

Even though there is a range with an invalid calibration value, that range is not selected. Select the range with
the invalid calibration value and calibrate it.

E3313

Failed to calibrate.

Check that the module is connected properly. Check the wiring, rated input, and etc.

E3314

For xxx is invalid.

Enter the correct value.

E3331

There is no module. Or there are many modules.

Several modules exist when setting up the network. Specify only one module.

E3337

The address is invalid.

Properly set the combination of the IP address, subnet mask, and default gateway.

E3338

Can not set the network address.

An error occurred while setting the address.

E3339

Modules not found.

Set the module’s dipswitch and turn DARWIN ON.

Check that the cables are connected properly.

Error Messages <Historical Viewer>

No.

Message/Corrective action

E3101

No data.

Valid data do not exist.

E3102

No channels.

Valid channel does not exist.

Error Messages <Remote Monitor>

No.

Message/Corrective action

E3558

Connection failure. Please check the host name, port No.,and server.
Confirm whether the monitor server is running. Check whether the host name and port number of the PC that