Yokogawa DAQWORX User Manual

Page 92

Advertising
background image

4-45

IM WX102-01E

1

2

3

4

5

6

7

8

9

10

11

Index

DAR

WIN Hardware Configurator

4.22 Setting Burn-out, RJC, and (for DR Only)

Recording Colors

Open the Alarm Setup setting screen (see below) for Burn-out, Reference Junction

Compensation, and (for DR Only) Recording Colors as follows: Click the SETUP tab

and select Channel from the SETUP Setting contents box, or select from the menubar

Settings > SETUP (Basic) Settings > Relay > and Burn-out, RJC, or Recording Colors.

Select a SETUP topic

SETUP tab

Burn-out setting

Select RJC

Recording color

(for DR only).

Click a color to

display the color

dialog box.

Copying Settings

Copy below settings to other channels as explained in Section 4.12.

Burn-out

Set the recording position for each channel when burn-out occurs. Click OFF, DOWN, or

UP. A blue circle marks the active setting.

• OFF :

The burn-out function is not actuated.

• DOWN : The output extends to the minimum value of the span.

• UP :

The output extends to the maximum value of the span.

Reference Junction Compensation (RJC)

Set either the internal or the external compensation for each channel in the RJC Type

setting space. A blue circle in the Burn-out setting area marks the active setting.

• INT : internal compensation is performed.

• EXT : external compensation is performed. For external compensation, set the voltage

to be compensated in the RJC Voltage setting area. Voltage to be externally

compensated: set in the range of –20000 to 20000 µV.

Recording Colors (for DR only)

To set the colors used for DR trend recording, click the color setting area to display the

Recording Colors setting screen. Select the desired channel color and click OK.