3 communication settings, 3 communication settings -4 – Yokogawa DAQWORX User Manual

Page 42

Advertising
background image

3-4

IM WX102-01E

3.3

Communication Settings

Use Software Configurator to set the communication method between PC and DA100/
DC100/DR.

1

Startup DAQ 32 Plus and select Software Configurator with the Launcher toolbar.

2

Click the Communications tab to display the Communications setting screen.

Select the desired communication method by clicking its setting frame, or click

Communications and select the desired method.

RS-232-C, RS-422-A/RS-485, GB-IB

3

Click in the setting windows to display the listbox from which you can choose a

value.

4

Set DA100/DC100/DR as follows.

• RS-232-C, RS-422-A/RS-485

If you use the setting windows for RS-232-C and RS-422-A/RS-485 the setting
depending positions of the dip switches on the module, will also be displayed.

After switching power OFF on the connected device, make sure to match the dip

switch positions on the modules with those on the setting screen.

• GP-IB

After switching power on the connected device OFF, make sure for the GP-IB that

the rotary switch on the module matches the address displayed on screen.

Ethernet

3

Set IP address of the connected device (DA100/DC100/DR).

Note

• Only change the dipswitch combination on the connected device, after power on the device

is turned OFF.

• If settings don’t match module settings a Communication error message will be displayed.