COMMAND DETAILS
41
Query Example
:CONF:AUTO:LOAD?
1
Auto load is On.
:CONFigure:AUTO:MODE
All channels
Description
Configures the Auto Load mode as (run) Program
or Load.
Syntax
:CONFigure:AUTO:MODE PROGRAM/0, LOAD/1
Parameter
PROGRAM/0, LOAD/1
Auto Load Mode
PROGRAM/0
PROGRAM
LOAD/1
LOAD
Example
:CONF:AUTO:MODE 1
Configures Auto Load to
LOAD
Query Syntax
:CONFigure:AUTO:MODE?
Return Parameter <NR1>
Auto Load Type Status
0
PROGRAM MODE
1
LOAD MODE
Query Example
:CONF:AUTO:MODE?
1
Auto load mode is to
LOAD mode.
:CONFigure:SOUND
Channel Specific
Command
Description
Sets the sound of each load module on or off.
Syntax
:CONFigure:SOUND {OFF|0|ON|1}
Parameter
OFF/0
Off
ON/1
On
Example
:CONF:SOUND ON
Configures the sound for
the specific channel to
On.
Query Syntax
:CONFigure:SOUND?