5-26

Using the I/O

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

PowerFlex 70, PowerFlex 700 with Standard Control, and PowerFlex 700H Drives

When using any of these products—which all contain INT (16-bit format)
data types—you will read from and write to a single data table address in
the controller.

Table 5.J PLC-5 Data Table Addresses for:

PowerFlex 70 Drives with Standard or Enhanced Control
PowerFlex 700 Drives with Standard Control
PowerFlex 700H Drives

Data Table Address Description

N9:0

Logic Status (see

Appendix D

)

N9:1

Speed Feedback

N9:2

Value of parameter assigned to Parameter 310 [Data Out A1]

N9:3

Value of parameter assigned to Parameter 311 [Data Out A2]

N9:4

Value of parameter assigned to Parameter 312 [Data Out B1]

N9:5

Value of parameter assigned to Parameter 313 [Data Out B2]

N9:6

Value of parameter assigned to Parameter 314 [Data Out C1]

N9:7

Value of parameter assigned to Parameter 315 [Data Out C2]

N9:8

Value of parameter assigned to Parameter 316 [Data Out D1]

N9:9

Value of parameter assigned to Parameter 317 [Data Out D2]

N10:0

Logic Command (see

Appendix D

)

N10:1

Speed Reference

N10:2

Value of parameter assigned to Parameter 300 [Data In A1]

N10:3

Value of parameter assigned to Parameter 301 [Data In A2]

N10:4

Value of parameter assigned to Parameter 302 [Data In B1]

N10:5

Value of parameter assigned to Parameter 303 [Data In B2]

N10:6

Value of parameter assigned to Parameter 304 [Data In C1]

N10:7

Value of parameter assigned to Parameter 305 [Data In C2]

N10:8

Value of parameter assigned to Parameter 306 [Data In D1]

N10:9

Value of parameter assigned to Parameter 307 [Data In D2]