Host DPI Parameter Object

Class Code

To access ‘Device’ parameters, use the DPI Parameter Object (Class Code
0x93).

Important: The Host DPI Parameter Object is supported only when the

adapter is used with a PowerFlex 750-Series drive.

Instances

The number of instances depends on the number of parameters in the device.
The total number of parameters can be read in Instance 0, Attribute 0.

Class Attributes

Hexadecimal

Decimal

0x9F

159

Instances (Hex.)

(Dec.)

Device

Example Description

0x0000…0x3FFF

0…16383

Reserved

16384

Class Attributes (Adapter)

0x4000…0x43FF

16384…17407

Adapter

16385

Adapter Parameter 1 Attributes

0x4400…0x47FF

17408…18431

DPI Port 1

16386

Adapter Parameter 2 Attributes

0x4800…0x4BFF

18432…19455

DPI Port 2

0x4C00…0x4FFF 19456…20479

DPI Port 3

17408

Class Attributes (HIM)

0x5000…0x53FF

20480…21503

DPI Port 4

17409

HIM Parameter 1 Attributes

0x5400…0x57FF

21504…22527

DPI Port 5

17410

HIM Parameter 2 Attributes

0x5800…0x5BFF

22528…23551

DPI Port 6

0x5C00…0x5FFF 23552…24575

DPI Port 7

0x6000…0x63FF

24576…25599

DPI Port 8

0x6400…0x67FF

25600…26623

DPI Port 9

0x6800…0x6BFF

26624…27647

DPI Port 10

0x6C00…0x6FFF 27648…28671

DPI Port 11

0x7000…0x73FF

28672…29695

DPI Port 12

0x7400…0x77FF

29696…30719

DPI Port 13

0x7800…0x7BFF

30720…31743

DPI Port 14

Attribute ID

Access Rule Name

Data Type

Description

0

Get

Number of Instances

WORD

Number of parameters in the device

1

Set

Write Protect Password

WORD

0 = Password disabled
n = Password

2

Set

NVS Command Write

BYTE

0 = No Operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory

3

Get

NVS Parameter Value Checksum

WORD

Checksum of all parameter values in a user set in NVS

4

Get

NVS Link Value Checksum

WORD

Checksum of parameter links in a user set in NVS

5

Get

First Accessible Parameter

WORD

First parameter available if parameters are protected by
passwords. A ‘0’ indicates all parameters are protected.

7

Get

Class Revision

WORD

2 = DPI

8

Get

First Parameter Processing Error

WORD

The first parameter that has been written with a value
outside of its range. A ‘0’ indicates no errors.

9

Set

Link Command

BYTE

0 = No Operation
1 = Clear All Parameter Links (This does not clear links