Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 56

Advertising
background image

4-20

Configuring the I/O

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

6. Under Connection Parameters, edit the following information.

Depending on the size of the drive’s Reference/Feedback and the number
of Datalinks used in your I/O configuration,

Table 4.A

,

Table 4.B

, or

Table 4.C

defines the number of 16-bit words that you need to enter for

the Input Size and Output Size boxes.

Table 4.A Drives with 16-bit Reference/Feedback and 16-bit Datalinks

These products include the following:

Table 4.B Drives with 16-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

Box

Assembly Instance

Size

Input

1
(This value is required.)

The value will vary based on your application
(setting of Parameters 13 - [DPI I/O Cfg] and 26 -
[M-S Output]
) and the size (16-bit or 32-bit) of the
Reference/Feedback and Datalinks in the drive. See

Table 4.A

,

Table 4.B

or

Table 4.C

.

Output

2
(This value is required.)

The value will vary based on your application
(setting of Parameters 13 - [DPI I/O Cfg] and 25 -
[M-S Input]
) and the size (16-bit or 32-bit) of the
Reference/Feedback and Datalinks in the drive. See

Table 4.A

,

Table 4.B

or

Table 4.C

.

Configuration

6
(This value is required.)

0 (This value is required.)

• PowerFlex 70 drives with standard or enhanced control

• SMC Flex smart motor controllers

• PowerFlex 700 drives with standard control

• SMC-50 smart motor controllers

• PowerFlex 700H drives

Logic
Command/
Status

Ref/Fdbk
(16-bit)

Datalinks (16-bit)

User Configured Settings

A

B

C

D

Size in Words

Par. 13 -
[DPI I/O Cfg]

Par. 25 -
[M-S Input]

Par. 26 -
[M-S Output]

Input

Output

4

2

…0 0001

…0 0001

…0 0001

6

4

…0 0011

…0 0011

…0 0011

8

6

…0 0111

…0 0111

…0 0111

10

8

…0 1111

…0 1111

…0 1111

12

10

…1 1111

…1 1111

…1 1111

• PowerFlex 700 drives with vector control

• PowerFlex Digital DC drives

• PowerFlex 700L drives with 700 control

Logic
Command/
Status

Ref/Fdbk
(16-bit)

Datalinks (32-bit)

User Configured Settings

A

B

C

D

Size in Words

Par. 13 -
[DPI I/O Cfg]

Par. 25 -
[M-S Input]

Par. 26 -
[M-S Output]

Input

Output

4

2

…0 0001

…0 0001

…0 0001

8

6

…0 0011

…0 0011

…0 0011

12

10

…0 0111

…0 0111

…0 0111

16

14

…0 1111

…0 1111

…0 1111

20

18

…1 1111

…1 1111

…1 1111