Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 48

Advertising
background image

4-12

Configuring the I/O

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

c.

Click Save to save the configuration to a file on your computer.

To be sure that the present project configuration values are saved,
RSLogix 5000 software prompts you to upload them. Click Yes to
upload and save the values.

Correlate the Drive with the Controller

You must now correlate the drive settings to the RSLogix 5000 project I/O
settings so that they match. This requires loading the project I/O settings
into the drive.

1. In the treeview under I/O Configuration, right-click the drive profile (for

this example, My_PowerFlex_70_EC_Drive) and choose Properties.

2. Click the Drive tab.

3. Click Connect to Drive to begin the correlation process.

The Connect To Drive screen appears.

4. Browse the communication path to the drive and select the drive.

5. Click OK.

After the drive configuration data has been verified, a pop-up dialog
box appears, which synchronizes ports from the online drive to the
project to be sure that correct Datalinks are assigned.

6. Click OK.

If the Differences Found screen appears—which is typical, click
Download. This will download the project settings from the controller
to the drive and its connected adapter. If Upload is clicked, the drive
and adapter settings are uploaded to the controller.