Message Structure for Execute_DH+

The adapter supports the following PCCC command types:

For more information regarding PCCC commands, see DF1 Protocol and
Command Set Manual, publication 1770-6.5.16

.

Request

Response

Name

Data Type Description

Name

Data Type Description

DLink

UINT

Destination Link ID

DLink

UINT

Destination Link ID

DSta

USINT

Destination Station number

DSta

USINT

Destination Station number

DUser

USINT

Destination “User” number

DUser

USINT

Destination “User” number

SLink

UINT

Source Link ID

SLink

UINT

Source Link ID

SSta

USINT

Source Station number

SSta

USINT

Source Station number

SUser

USINT

Source User number

SUser

USINT

Source User number

CMD

USINT

Command byte

CMD

USINT

Command byte

STS

USINT

0

STS

USINT

Status byte

TNSW

UINT

Transport word

TNSW

UINT

Transport word. Same value as the request.

FNC

USINT

Function code; not used for all CMDs

EXT_STS

USINT

Extended status; not used for all CMDs

PCCC_
params

ARRAY of
USINT

CMD/FNC specific parameters

PCCC_
results

ARRAY of
USINT

CMD/FNC specific result data

CMD

FNC

Description

0x06

0x03

Identify host and some status

0F

67

PLC-5 typed write

0F

68

PLC-5 typed read

0F

95

Encapsulate other protocol

0F

A2

SLC 500 protected typed read with 3 address fields

0F

AA

SLC 500 protected typed write with 3 address fields

0F

A1

SLC 500 protected typed read with 2 address fields

0F

A9

SLC 500 protected typed write with 2 address fields

0F

00

Word range read

0F

01

Word range write