Adapter Parameters

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

25

[M-S Input]

Sets the Master-Slave input data. This data is
produced by the scanner and consumed by the
adapter.

Default:

xxx0 0001

Bit Values:

0 = I/O Disabled
1 = I/O Enabled

Type:

Read/Write

Reset Required: Yes

26

[M-S Output]

Sets the Master-Slave output data. This data is
produced by the adapter and consumed by the
Master device (for example, scanner).

Default:

xxx0 0001

Bit Values:

0 = I/O Disabled
1 = I/O Enabled

Type:

Read/Write

Reset Required: Yes

27

[Ref Adjust]

Sets the percent scale factor for the Reference
received from the network.

Default:

100.00%

Minimum:

0.00%

Maximum:

200.00%

Type:

Read/Write

Reset Required: No

Parameter

No.

Name and Description

Details

Bit
Definition

Not

Used

Not

Used

Not

Used

Dat

a

link D

In

put

Dat

a

link C

In

put

Data

link B

Inpu

t

Data

link A

Inpu

t

Cmd/Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

Bit
Definition

Not Used

Not Used

Not Used

Datalink D

O

ut

put

Datalink C

O

ut

put

Dat

alink B Out

put

Dat

alink A Out

put

Cmd/

Ref

Default

x

x

x

0

0

0

0

1

Bit

7

6

5

4

3

2

1

0

!

ATTENTION: To guard against equipment damage and/or personal injury, note
that changes to Parameter 27 - [Ref Adjust] take effect immediately. A drive
receiving its Reference from the adapter will receive the newly scaled
Reference, resulting in a change of speed.