There is no need to – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 61

Advertising
background image

Configuring the I/O

4-25

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

For this example, the adapter I/O parameters are set to these values.

2. Reset the adapter (see

Resetting the Adapter on page 3-7

) or power

cycle the drive.

For the drive speed reference and Datalink parameter values and the
adapter setup parameter values, see

Drive and Adapter Parameter

Settings on page 5-24

.

Use RSNetWorx for ControlNet Software to Configure the I/O and Save
It to the Controller

To establish an I/O configuration that can be used between the controller
and drive over a ControlNet network, you must first create an I/O image for
the PLC-5/40C controller’s built-in scanner.

1. Start RSNetWorx for ControlNet software.

2. In the RSNetWorx for ControlNet window, select File > New to display

the New File screen.

3. Select ‘ControlNet Configuration’ as the network configuration type.

4. Click OK.

5. Select Network > Online to display the Browse for Network screen.

6. Expand the communication path from your computer to the PLC-5/40C

controller.

Adapter Parameter No.

Setting

13 - [DPI I/O Cfg]

xxxx xxxx xxx1 1111

25 - [M-S Input]

xxxx xxxx xxx1 1111

26 - [M-S Output]

xxxx xxxx xxx1 1111