Controllogix controller example, Controllogix controller example -2 – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 38

Advertising
background image

4-2

Configuring the I/O

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

The Configure Drivers screen reappears with the new driver in the
Configured Drivers list.

7. Click Close to close the Configure Drivers screen.

8. Keep RSLinx running and verify that your computer recognizes the

drive.

a. Select Communications > RSWho.

b. In the menu tree, click ‘+’ next to the ControlNet driver.

ControlLogix Controller
Example

After the adapter is configured, the connected drive and adapter will be a
single node on the network. This section provides the steps needed to
configure a simple ControlNet network (see

Figure 4.1

). In our example, we

will configure a ControlLogix controller with 1756-CNBR (Series D)
bridge to communicate with a drive using Logic Command/Status,
Reference/Feedback, and 16 Datalinks (8 to read and 8 to write) over the
network.

Figure 4.1

Example ControlLogix Controller ControlNet Network

ControlLogix Controller

with 1756-CNBR Bridge

PowerFlex 70 Drive with

20-COMM-C Adapter

Computer with

ControlNet Connection

(optional redundancy)

Channel A

Channel B

ControlNet
Network

TIP: Information for PowerFlex 750-Series drives has been added to this
manual where it is applicable.