Viewing and clearing events, Using the him to view and clear events, Viewing and clearing events -6 – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 198

Advertising
background image

7-6

Troubleshooting

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

Viewing and Clearing
Events

The adapter has an event queue to record significant events that occur in the
operation of the adapter. When such an event occurs, an entry is put into the
event queue. You can view the event queue with any of these drive
configuration tools:

• LCD PowerFlex 7-Class HIM

• Connected Components Workbench software, version 1.02 or later

• DriveExplorer software, version 2.01 or later

• DriveExecutive software, version 1.01 or later

The event queue can contain up to 32 entries. Eventually the event queue
will become full, since its contents are retained through adapter resets. At
that point, a new entry replaces the oldest entry. Only an event queue clear
operation or adapter power cycle will clear the event queue contents.

Resetting the adapter to defaults has no effect on the event queue.

Using the HIM to View and Clear Events

Step

Example Screen

Viewing Events

1. Access parameters in the adapter.

See

Using the PowerFlex 7-Class HIM to Access Parameters on

page 3-2

.

2. Press the

or

key to scroll to Diagnostics.

3. Press the

(Enter) key to display the Diagnostics menu in the

adapter.

4. Repeat steps 2 and 3 to enter the Events option and then View

Event Queue option.

5. Press the

or

key to scroll through events.

The most recent event is Event 1.

Clearing Events

1. Access parameters in the adapter.

See

Using the PowerFlex 7-Class HIM to Access Parameters on

page 3-2

.

2. Press the

or

key to scroll to Diagnostics.

3. Press the

(Enter) key to display the Diagnostics menu in the

adapter.

4. Repeat steps 2 and 3 to enter the Events option and then the

Clear Event option or Clr Event Queue option.

A message will pop up to confirm that you want to clear the
message or queue.

5. Press the

(Enter) key to confirm your request.

If Clr Event Queue was selected, all event queue entries will then
display ‘No Event’.

Main Menu:

Diagnostics

Parameter
Device Select

Event Q:

1

E3

Ping Time Flt

Dgn: Events
View Event Queue
Clear Event

Clr Event Queue

Advertising
This manual is related to the following products: