Register object, Class code, Services – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 214: Instances, Class attributes, Instance attributes

Advertising
background image

C-4

ControlNet Objects

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

Register Object

Class Code

Services

Instances

Class Attributes

Instance Attributes

Important: Setting a Register object attribute can only be done when the

Control Timeout (class attribute 100) has been set to a non-zero
value.

Hexadecimal

Decimal

0x07

7

Service Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

Yes

Set_Attribute_Single

Instance

Description

1

All I/O data being read from the DPI device (read-only)

2

All I/O data written to the DPI device (read/write)

3

Logic Status and Feedback data (read-only)

4

Logic Command and Reference data (read/write)

5

Datalink A (input data from device to scanner) (read only)

6

Datalink A (output data from scanner to device) (read/write)

7

Datalink B (input data from device to scanner) (read only)

8

Datalink B (output data from scanner to device) (read/write)

9

Datalink C (input data from device to scanner) (read only)

10

Datalink C (output data from scanner to device) (read/write)

11

Datalink D (input data from device to scanner) (read only)

12

Datalink D (output data from scanner to device) (read/write)

13

Logic Status and Feedback Data (read-only)

14

Mask

(1)

(read/write)

(1)

The mask command word is set to the value of the first word of the data where there are ones in the
second word of the data. Command = (word 1 and not word 2) or (word 1 and word 2). This only controls
specified bits in the Logic Command data to the DPI product and does not change the Reference value.

15

Logic Status (read-only)

16

Logic Command (read/write)

17

Feedback (read-only)

18

Reference (read/write)

Attribute ID

Access Rule Name

Data Type Description

100

Set

Control Timeout

WORD

Control timeout in seconds

Attribute ID

Access Rule Name

Data Type

Description

1

Get

Bad Flag

BOOL

If set to 1, then attribute 4 may contain invalid data.
0 = good
1 = bad

2

Get

Direction

BOOL

Direction of data transfer
0 = Producer Register (drive to network)
1 = Consumer Register (network to drive)

3

Get

Size

WORD

Size of register data in bits

4

Conditional

(1)

Data

ARRAY of BITS

Data to be transferred

(1)

For this attribute, the Access Rule is Get if Direction = 0. The Access Rule is Set if Direction = 1.