Parameter object, Class code, Services – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 215: Instances, Class attributes

Advertising
background image

ControlNet Objects

C-5

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

Parameter Object

Class Code

Important: This object is not supported when the adapter is used with a

PowerFlex 750-Series drive.

Services

Instances

The number of instances depends on the number of parameters in the DPI
drive. The adapter parameters are appended to the list of drive parameters.
The total number of parameters can be read in Instance 0, Attribute 2.

Class Attributes

Hexadecimal

Decimal

0x0F

15

Service Code Implemented for:

Service Name

Class

Instance

0x01

Yes

Yes

Get_Attributes_All

0x05

Yes

No

Reset

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

0x4B

No

Yes

Get_Enum_String

Instance

Description

0

Class Attributes

1

Drive Parameter 1 Attributes

n

Last Drive Parameter n Attributes

(1)

(1)

n represents the number of parameters in the drive.

n + 1

Adapter Parameter 1 Attributes

n + m

Last Adapter Parameter m Attributes

(2)

(2)

m represents the number of parameters in the adapter.

Attribute ID Access Rule Name

Data Type

Description

1

Get

Revision

WORD

1

2

Get

Max Instance

WORD

Number of parameters

8

Get

Parameter Class Descriptor

WORD

0 = False, 1 = True
Bit 0 = Supports parameter instances
Bit 1 = Supports full attributes
Bit 2 = Must do NVS save command
Bit 3 = Parameters are stored in NVS

9

Get

Configuration Assembly Instance

WORD

0

10

Set

Native Language

BYTE

0 = English
1 = French
2 = Spanish
3 = Italian
4 = German
5 = Japanese
6 = Portuguese
7 = Mandarin Chinese
8 = Russian
9 = Dutch