Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 163

Advertising
background image

Using Explicit Messaging

6-35

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

PLC-5 Controller Example Ladder Logic Program to Write Multiple
Parameters

A Generic Bi-Directional scattered write message is used to write to
multiple parameters. This write message example writes the following
values to these five parameters.

See

DPI Parameter Object on page C-16

(Class code 0x93) or

Host DPI

Parameter Object on page C-30

(Class code 0x9F) for parameter

numbering.

Important: See

Table 6.A on page 6-2

for limitations of PowerFlex 7-Class

and PowerFlex 750-Series drives when using DPI Parameter
Object Class code 0x93 or Host DPI Parameter Object Class
code 0x9F for explicit messaging.

Figure 6.43 Example Ladder Logic to Write Multiple Parameters

Important: If the explicit message scattered write must be written

continuously, then use a separate Generic Set service explicit
message single write for each parameter using DPI Parameter
Object Class code 0x93 or Host DPI Parameter Object Class
code 0x9F and attribute A (see

page 6-27

). Attribute A writes to

RAM—not NVS (EEPROM) memory. This example scattered
write message writes to NVS. Over time, continuous writes will
exceed the EEPROM life cycle and cause the drive to
malfunction.

PowerFlex 7-Class
Drive Parameter

Write Value

PowerFlex 750-Series
Drive Parameter

Write Value

141 - [Accel Time 2]

11.1 Sec.

536 - [Accel Time 2]

11.1 Sec.

143 - [Decel Time 2]

22.2 Sec.

538 - [Decel Time 2]

22.2 Sec.

105 - [Preset Speed 5]

33.3 Hz.

725 - [Zero Position]

33

106 - [Preset Speed 6]

44.4 Hz.

21555 - [Port 5: Analog In0 Hi]

5.5

107 - [Preset Speed 7]

55.5 Hz.

780 - [PTP Setpoint]

-75,555