4-36

Configuring the I/O

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

Table 4.H Drives with 16-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

Table 4.I

Drives with 32-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

11. Because N files are used in

Using the I/O

,

Chapter 5

and memory files

cannot be used for 32-bit REAL (floating point) data, the default Input
Address M1:e.3 and Output Address M0:e.3 will need to be converted
later using COP instructions in the ladder logic program. For now, leave
these address fields at their defaults, and click OK.

An address row (in blue text) will be added below the PowerFlex 70 EC
drive row.

12. Select File > Save to save the I/O configuration file to the 1747-SCNR

scanner.

The Save Configuration dialog box appears.

• PowerFlex 700 drives with vector control

• PowerFlex Digital DC drives

• PowerFlex 700L drives with 700 control

Logic
Command/
Status

Ref/Fdbk
(16-bit)

Datalinks (32-bit)

User Configured Settings

A

B

C

D

Size in Words

Par. 13 -
[DPI I/O Cfg]

Par. 25 -
[M-S Input]

Par. 26 -
[M-S Output]

Input

Output

4

2

…0 0001

…0 0001

…0 0001

8

6

…0 0011

…0 0011

…0 0011

12

10

…0 0111

…0 0111

…0 0111

16

14

…0 1111

…0 1111

…0 1111

20

18

…1 1111

…1 1111

…1 1111

• PowerFlex 700S drives with Phase I or Phase II control

• PowerFlex 753 drives

• PowerFlex 700L drives with 700S control

• PowerFlex 755 drives

Logic
Command/
Status

Ref/Fdbk
(32-bit)

Datalinks (32-bit)

User Configured Settings

A

B

C

D

Size in Words

Par. 13 -
[DPI I/O Cfg]

Par. 25 -
[M-S Input]

Par. 26 -
[M-S Output]

Input

Output

6

4

…0 0001

…0 0001

…0 0001

10

8

…0 0011

…0 0011

…0 0011

14

12

…0 0111

…0 0111

…0 0111

18

16

…0 1111

…0 1111

…0 1111

22

20

…1 1111

…1 1111

…1 1111

TIP: When both Save Type choices are available, we recommend to
click the ‘Optimize and re-write schedule for all connections’.