Dpi time object, Class code, Services – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 238: Instances, Class attributes, C-28

Advertising
background image

C-28

ControlNet Objects

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

DPI Time Object

Class Code

Services

Instances

The number of instances depends on the number of timers in the device.
Instance 1 is always reserved for a real-time clock although a device may not
support it. The total number of timers can be read in Instance 0, Attribute 2.

Class Attributes

Hexadecimal

Decimal

0x9B

155

Service Code Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

Yes

Set_Attribute_Single

Instances (Hex.)

(Dec.)

Device

Example Description

0x0000…0x3FFF

0…16383

Host

0

Class Attributes (Drive)

0x4000…0x43FF

16384…17407 Adapter

1

Real Time Clock (Predefined)
(not always supported)

0x4400…0x47FF

17408…18431 DPI Port 1

2

Timer 1

0x4800…0x4BFF

18432…19455 DPI Port 2

3

Timer 2

0x4C00…0x4FFF

19456…20479 DPI Port 3

0x5000…0x53FF

20480…21503 DPI Port 4

0x5400…0x57FF

21504…22527 DPI Port 5

0x5800…0x5BFF

22528…23551 DPI Port 6

0x5C00…0x5FFF

(1)

(1)

These instances are supported only when the adapter is used with a PowerFlex 750-Series drive.

23552…24575 DPI Port 7

0x6000…0x63FF

(1)

24576…25599 DPI Port 8

0x6400…0x67FF

(1)

25600…26623 DPI Port 9

0x6800…0x6BFF

(1)

26624…27647 DPI Port 10

0x6C00…0x6FFF

(1)

27648…28671 DPI Port 11

0x7000…0x73FF

(1)

28672…29695 DPI Port 12

0x7400…0x77FF

(1)

29696…30719 DPI Port 13

0x7800…0x7BFF

(1)

30720…31743 DPI Port 14

Attribute ID Access Rule

Name

Data Type

Description

1

Get

Class Revision

WORD

Revision of object

2

Get

Number of Instances

WORD

Number of timers in the object, excluding the
real-time clock that is predefined.

3

Get

First Device Specific Timer

WORD

Instance of the first timer that is not predefined.

4

Set

Time Command Write

BYTE

0 = No Operation
1 = Clear all timers (Does not clear the real-time

clock or read only timers)

5

Get

Number of Supported Time
Zones

WORD

Number of time zones described in the Time
Zone List attribute.

6

Get

Time Zone List

STRUCT

Identifies a time zone.

7

Get/Set

Active Time Zone ID

WORD

The ID field of the Time Zone List structure for
the desired time zone.

Advertising