Configuring the I/O

4-21

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

Table 4.C Drives with 32-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

When using Datalinks, up to 8 drive [Data In xx] parameters (300…307)
and/or up to 8 [Data Out xx] parameters (310…317) must be assigned to
point to the appropriate drive parameters for your application.

7. After setting the information in the drive’s New Module screen, click

OK.

The Module Properties screen appears.

8. Click the Connection tab.

9. In the ‘Requested Packet Interval (RPI)’ box, set the value to 5.0

milliseconds or greater.

This value determines the maximum interval that a controller should
use to move data to and from the adapter. To conserve bandwidth, use
higher values for communicating with low priority devices. For this
example, leave the ‘Inhibit Module’ and ‘Major Fault…’ boxes
unchecked.

10. Click OK.

• PowerFlex 700S drives with Phase I or Phase II control

• PowerFlex 753 drives

• PowerFlex 700L drives with 700S control

• PowerFlex 755 drives

Logic
Command/
Status

Ref/Fdbk
(32-bit)

Datalinks (32-bit)

User Configured Settings

A

B

C

D

Size in Words

Par. 13 -
[DPI I/O Cfg]

Par. 25 -
[M-S Input]

Par. 26 -
[M-S Output]

Input

Output

6

4

…0 0001

…0 0001

…0 0001

10

8

…0 0011

…0 0011

…0 0011

14

12

…0 0111

…0 0111

…0 0111

18

16

…0 1111

…0 1111

…0 1111

22

20

…1 1111

…1 1111

…1 1111

TIP: For instructions on configuring the I/O for the adapter using
Parameter 13 - [DPI I/O Cfg] and its Master-Slave hierarchy using
Parameters 25 - [M-S Input] and 26 - [M-S Output], see

Setting the I/O Configuration on page 3-3

.