E_response, Figure 6.22 – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 149

Advertising
background image

Using Explicit Messaging

6-21

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

Figure 6.22 Example Scattered Write Response Data for PowerFlex 7-Class Drive

The PowerFlex 750-Series drive uses 32-bit integer and REAL parameters.
A COP command must be used to copy the 32-bit integer and REAL values
to the Scattered_Write_Request integer array.

Figure 6.23

shows the ladder

logic used for this example. If the parameter data type is a REAL, then the
source tag is a REAL. If the parameter data type is a 32-bit integer, then the
source tag is a DINT. See the drive documentation to determine the
parameter data type (32-bit integer or REAL).

Figure 6.23 Example Ladder Logic to Copy Request Data for PowerFlex 750-Series

Drive

Advertising
This manual is related to the following products: