Setting the node address, Setting the i/o configuration, Setting the node – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 31: For details

Advertising
background image

Configuring the Adapter

3-3

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

Setting the Node Address

If the adapter Node Address switches (

Figure 2.1

) are set to ‘00’ (Program)

the value of Parameter 03 - [CN Addr Cfg] determines the node address.
When in any other combination of positions, the Node Address switches
determine the node address.

1. Set the value of Parameter 03 - [CN Addr Cfg] to a unique node

address.

2. Reset the adapter (see

Resetting the Adapter on page 3-7

).

When the node address is correctly configured and the adapter is connected
to an operational network, the NET A status indicator should be steady
green or flashing green.

Setting the I/O
Configuration

The I/O configuration determines the data that is sent to and from the drive.
Logic Command/Status, Reference/Feedback, and Datalinks may be
enabled or disabled. (Datalinks allow you to read/write directly to
parameters in the drive using implicit I/O.) A ‘1’ enables the I/O and a ‘0’
disables the I/O.

1. Set the bits in Parameter 13 - [DPI I/O Cfg].

Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.

2. If a controller is used to control the drive, set adapter Parameters 25 -

[M-S Input] and 26 - [M-S Output] for Master-Slave Hierarchy.

For details, see

Setting Master-Slave Hierarchy on page 3-4

.

3. If Logic Command/Reference is enabled, configure the parameters in

the drive to accept the Logic Command and Reference from the adapter.

For example, set Parameter 90 - [Speed Ref A Sel] in a PowerFlex 70 or
700 drive to ‘22’ (DPI Port 5) so that the drive uses the Reference from
the adapter. Also, verify that the mask parameters (for example,
Parameter 276 - [Logic Mask]) in the drive are configured to receive the
desired logic from the adapter. See the documentation for your drive for
details.

Port 5 Device

20-COMM-C

Parameter #: 03
CN Addr Cfg

2

0 <> 63

Default = 02

Bit

Description

0

Logic Command/Reference (Default)

1

Datalink A

2

Datalink B

3

Datalink C

4

Datalink D

5…15

Not Used

Port 5 Device

20-COMM-C

Parameter #: 13
DPI I/O Cfg
x x x x x x x x x x x 0 0 0 0

1

Cmd/Ref

b00

Advertising
This manual is related to the following products: