Setting the Node Address
Switches

Set the adapter Node Address switches (

Figure 2.1

) by rotating the switches

to the desired value for each digit.

Important: Each node on the ControlNet network must have a unique

address. Set the node address before power is applied because
the adapter uses the node address it detects when it first
receives power. To change a node address, you must set the new
value and then remove and reapply power to (or reset) the
adapter.

Figure 2.1

Setting Adapter Node Address Switches

The Node Address switch settings can be verified by viewing Parameter 04
- [CN Addr Act]
or Diagnostic Device Item number 27 (

page 7-5

) with any

of the following drive configuration tools:

• PowerFlex HIM

• Connected Components Workbench software, version 1.02 or later

• DriveExplorer software, version 2.01 or later

• DriveExecutive software, version 3.01 or later

Setting

Description

00

If the Node Address switches are set to ‘00’ (Program), the adapter uses the value
stored in Parameter 03 - [CN Addr Cfg] for the node address. See

Setting the Node

Address on page 3-3

.

01…99

Node address used by the adapter. The default switch setting is 02.

2

1

0

9

8

3

4

5

6

7

2

1

0

9

8

3

4

5

6

7

S2

(Tens Digit)

S3

(Ones Digit)

20-COMM-C coax
adapter shown