Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 147

Advertising
background image

Using Explicit Messaging

6-19

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

ControlLogix Controller – Formatting a Message to Write Multiple Parameters Using
RSLogix 5000 Software, Any Version

Figure 6.20 Scattered Write Multiple Message Configuration Screens

The following table identifies the data that is required in each box to
configure a message to write multiple parameters.

Configuration Tab

Example Value

Description

Message Type
Service Type

(1)

Service Code

(1)

Class
Instance
Attribute
Source Element

Source Length
Destination

CIP Generic
Custom
4c (Hex.)
93 or 9F (Hex.)

(3)

0 (Dec.)
0 (Hex.)
Scattered_Write_Request

(4)

30

(4)

Scattered_Write_Response

Used to access Parameter Object in the adapter.
Required for scattered messages.
Code for the requested service.
Class ID for the DPI Parameter Object.
Required for scattered messages.
Required for scattered messages.
Name of the tag for any service data to be sent from

scanner or bridge to the adapter/drive.

Number of bytes of service data to be sent in the message.
The tag where the data that is read is stored.

Communication Tab

Example Value

Description

Path

(2)

My_PowerFlex_Drive

The path is the route that the message will follow.

Tag Tab

Example Value

Description

Name

Scattered_Write_Message

The name for the message.

(1)

The default setting for Service Type is ‘Custom’, enabling entry of a Service Code not available from the Service Type pull-down
menu. When choosing a Service Type other than ‘Custom’ from the pull-down menu, an appropriate Hex. value is automatically
assigned to the Service Code box which is dimmed (unavailable).

(2)

Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder.

(3)

See

Table 6.A on page 6-2

for limitations of PowerFlex 7-Class and PowerFlex 750-Series drives when using DPI Parameter Object

Class code 0x93 or Host DPI Parameter Object Class code 0x9F for explicit messaging.

(4)

In this example, we are writing to five parameters. Each parameter being written to requires an array of three INT registers.
Therefore, a controller tag was created with its Data Type field set to ‘INT[15]’. Also, the Source Length field on the Message
Configuration screen must correspond to the selected Data Type in bytes (for this example, 30 bytes for an INT[15] array).
Scattered write messages always assume that every parameter being written to is a 32-bit integer, regardless of its actual data
type. Maximum length is 132 bytes or 66 words which equates to 22 parameters. For parameter numbering, see

DPI Parameter

Object on page C-16

(Class code 0x93) or

Host DPI Parameter Object on page C-30

(Class code 0x9F).

Advertising
This manual is related to the following products: