Read multiple parameters – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 141

Advertising
background image

Using Explicit Messaging

6-13

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

Read Multiple Parameters

ControlLogix Controller Example Ladder Logic Program to Read Multiple
Parameters Using RSLogix 5000 Software, Any Version

A Scattered Read message is used to read the values of multiple parameters.
Up to 22 parameters can be read. This read message example reads the
values of these five parameters.

See

DPI Parameter Object on page C-16

(Class code 0x93) or

Host DPI

Parameter Object on page C-30

(Class code 0x9F) for parameter

numbering.

Important: See

Table 6.A on page 6-2

for limitations of PowerFlex 7-Class

and PowerFlex 750-Series drives when using DPI Parameter
Object Class code 0x93 or Host DPI Parameter Object Class
code 0x9F for explicit messaging.

Table 6.F Example Controller Tags to Read Multiple Parameters

Figure 6.12 Example Ladder Logic to Read Multiple Parameters

PowerFlex 7-Class Drive

PowerFlex 750-Series Drive

• Parameter 001 - [Output Freq]

• Parameter 003 - [Output Current]

• Parameter 006 - [Output Voltage]

• Parameter 012 - [DC Bus Voltage]

• Parameter 017 - [Analog In1 Value]

• Parameter 001 - [Output Freq]

• Parameter 007 - [Output Current]

• Parameter 137 - [Open Loop Fdbk]

• Parameter 21581 - [Port 5: Analog Out 0 Data]

• Parameter 260 - [Analog In0 Value]

Operand

Controller Tags for Read Multiple Message

Data Type

XIC

Execute_Scattered_Read_Message

BOOL

MSG

Scattered_Read_Message

MESSAGE

Advertising
This manual is related to the following products: