Configuring the I/O

4-31

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

Configuring Parameters for Network I/O

Because the I/O for the drive is defined in the next subsection

Use

RSNetWorx for ControlNet Software to Configure the I/O and Save It to the
1747-SCNR Scanner on page 4-31

, there is no need to configure any I/O

inside the RSLogix 500 project, version 7.00 or later, until using the I/O as
described in

Chapter 5

.

However, to get the adapter to operate with the I/O created in

Chapter 5

, you

need to configure the adapter to accept the I/O and drive to point to the
appropriate Datalinks.

1. Set adapter parameters 13 - [DPI I/O Cfg], 25 - [M-S Input], and 26 -

[M-S Output] to values that meet your application requirements.

For this example, the adapter I/O parameters are set to these values.

2. Reset the adapter (see

Resetting the Adapter on page 3-7

) or power

cycle the drive.

For the drive speed reference and Datalink parameter values and the
adapter setup parameter values, see

Drive and Adapter Parameter

Settings on page 5-40

.

Use RSNetWorx for ControlNet Software to Configure the I/O and Save
It to the 1747-SCNR Scanner

To establish an I/O configuration that can be used between the controller
and drive over a ControlNet network, you must first create an I/O image for
the SLC 500 controller’s 1747-SCNR scanner.

1. Start RSNetWorx for ControlNet software.

2. In the RSNetWorx for ControlNet window, select File > New to display

the New File screen.

3. Select ‘ControlNet Configuration’ as the network configuration type.

4. Click OK.

Adapter Parameter No.

Setting

13 - [DPI I/O Cfg]

xxxx xxxx xxx1 1111

25 - [M-S Input]

xxxx xxxx xxx1 1111

26 - [M-S Output]

xxxx xxxx xxx1 1111