D-8

Logic Command/Status Words

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

Logic Status Word

Logic Bits

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

Status

Description

x

Ready

0 = Not Ready (Par. 1403)
1 = Ready

x

Active

0 = Not Active (Running)
1 = Active

x

Command
Direction

0 = Reverse
1 = Forward

x

Actual Direction

0 = Reverse
1 = Forward

x

Accel

0 = Not Accelerating
1 = Accelerating

x

Decel

0 = Not Decelerating
1 = Decelerating

x

Alarm

0 = No Alarm (Par. 1380)
1 = Alarm

x

Fault

0 = No Fault (Par. 1351)
1 = Fault

x

At Speed

0 = Not At Reference
1 = At Reference

x

x

x

Local Control

(1)

000 = Port 0 (TB)
001 = Port 1
010 = Port 2
011 = Port 3
100 = Port 4
101 = Port 5
110 = Reserved
111 = No Local

x

x

x

x

Reference Source

0000 = Spd Ref A Auto (Par. 44)
0001 = Spd Ref B Auto (Par. 48)
0010 = Preset Spd 2 Auto
0011 = Preset Spd 3 Auto
0100 = Preset Spd 4 Auto
0101 = Preset Spd 5 Auto
0110 = Preset Spd 6 Auto
0111 = Preset Spd 7 Auto
1000 = Term Blk Manual
1001 = DPI 1 Manual
1010 = DPI 2 Manual
1011 = DPI 3 Manual
1100 = DPI 4 Manual
1101 = DPI 5 Manual
1110 = Reserved
1111 = Jog Ref

(1)

See ‘Owners’ in drive User Manual for further information.