9. In the RSNetWorx for ControlNet graph view window, right-click the

PLC-5/40C icon and choose Scanlist Configuration to display the
Scanlist Configuration screen.

10. Right-click the PowerFlex 70 EC drive row in the screen and choose

Insert Connection… to display the Connection Properties screen.

a. In this screen, leave the Connection Name box at the default value

shown.

b. For the Requested Packet Interval box, choose a value that is

suitable for your application, but is at least 5 ms.

c.

For the Input Size and Output Size boxes, use the pull-down menu
to choose the number of words that are required for your I/O.

The size will depend on the I/O that you enabled in the adapter
using Parameter 13 - [DPI I/O Cfg]. For this example, an Input
Size of ‘10’ and an Output Size of ‘10’ are selected.

Depending on the size of the drive’s Reference/Feedback and the
number of Datalinks used in your I/O configuration,

Table 4.D

,

Table

4.E

, or

Table 4.F

defines the number of 16-bit words that you need to

enter for the Input Size and Output Size boxes.