Using the I/O

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

Creating Ladder Logic Using the RSLogix 5000 Generic Profile, All
Versions

Drive and Adapter Parameter Settings

The following drive and adapter settings were used for the example ladder
logic program in this section.

Device

Parameter

Value

Description

PowerFlex 70
EC Drive

90 - [Speed Ref A Sel

22 (DPI Port 5)

Assigns 20-COMM-C/-Q to be used for the Reference.

300 - [Data In A1]

140

Points to Par. 140 - [Accel Time 1]

301 - [Data In A2]

142

Points to Par. 142 - [Decel Time 1]

302 - [Data In B1]

100

Points to Par. 100 - [Jog Speed]

303 - [Data In B2]

155

Points to Par. 155 - [Stop Mode A]

304 - [Data In C1]

101

Points to Par. 101 - [Preset Speed 1]

305 - [Data In C2]

102

Points to Par. 102 - [Preset Speed 2]

306 - [Data In D1]

103

Points to Par. 103 - [Preset Speed 3]

307 - [Data In D2]

104

Points to Par. 104 - [Preset Speed 4]

310 - [Data Out A1]

140

Points to Par. 140 - [Accel Time 1]

311 - [Data Out A2]

142

Points to Par. 142 - [Decel Time 1]

312 - [Data Out B1]

100

Points to Par. 100 - [Jog Speed]

313 - [Data Out B2]

155

Points to Par. 155 - [Stop Mode A]

314 - [Data Out C1]

101

Points to Par. 101 - [Preset Speed 1]

315 - [Data Out C2]

102

Points to Par. 102 - [Preset Speed 2]

316 - [Data Out D1]

103

Points to Par. 103 - [Preset Speed 3]

317 - [Data Out D2]

104

Points to Par. 104 - [Preset Speed 4]

PowerFlex
750-Series
Drive

(1)

545 - [Spd Ref A Sel]

Port 0: Port 6 Reference

Assigns 20-COMM-C/Q to be used for the Reference.

895 - [Data In A1]

Port 0: Accel Time 1

Points to Par. 535 in the drive.

896 - [Data In A2]

Port 0: Testpoint Sel 1

Points to Par. 970 in the drive.

897 - [Data In B1]

Port 5: Anlg Out1 Hi

Points to Par. 90 in Port 5 (I/O module).

905 - [Data Out A1]

Port 0: DC Bus Volts

Points to Par. 11 in the drive.

906 - [Data Out A2]

Port 0: Open Loop Fdbk

Points to Par. 137 in the drive.

907 - [Data Out B1]

Port 5: Anlg Out0 Data

Points to Par. 77 in Port 5 (I/O module).

20-COMM-C or
20-COMM-Q
Adapter

03 - [CN Addr Cfg]

2

Node address for the adapter.

13 - [DPI I/O Cfg]

xxx1 1111

Enables Cmd/Ref and Datalinks A…D.

25 - [M-S Input]

xxx1 1111

Configures the I/O Data to be transferred from the
controller on the network to the drive.

26 - [M-S Output]

xxx1 1111

Configures the I/O Data to be transferred from the
drive to the controller on the network.

(1)

In this example, the 20-COMM-C or 20-COMM-Q adapter/20-750-20COMM Communication Carrier Card is installed in Port 6, and a 24V I/O
module is installed in Port 5. Also, Data In B2…D2 (Parameters 898…902) and Data Out B2…D2 (Parameters 908…912) are enabled, but not
used.

TIP: Data In parameters are inputs into the drive that come from controller
outputs (for example, data to write to a drive parameter). Data Out
parameters are outputs from the drive that go to controller inputs (for
example, data to read a drive parameter).