Logic status word – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual
Page 250

D-4
Logic Command/Status Words
20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P
Logic Status Word
Logic Bits
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Status
Description
x
Active
0 = Not Active
1 = Active
x
Running
0 = Not Running
1 = Running
x
Command
Direction
0 = Reverse
1 = Forward
x
Actual Direction
0 = Reverse
1 = Forward
x
Accel
0 = Not Accelerating
1 = Accelerating
x
Decel
0 = Not Decelerating
1 = Decelerating
x
Jogging
0 = Not Jogging
1 = Jogging
x
Fault
0 = No Fault (Par. 323, 324, 325)
1 = Fault
x
Alarm
0 = No Alarm (Par. 326, 327, 328)
1 = Alarm
x
Flash Mode
0 = Not in Flash Mode
1 = In Flash Mode
x
Run Ready
0 = Not Ready to Run (Par. 156)
1 = Ready to Run
x
At Limit
(1)
0 = Not At Limit (Par. 304)
1 = At Limit
x
Tach Loss Sw
0 = Not Tach Loss Sw
1 = Tach Loss Sw
x
At Zero Spd
0 = Not At Zero Speed
1 = At Zero Speed
x
At Setpt Spd
0 = Not At Setpoint Speed
1= At Setpoint Speed
x
Enable
0 = Not Enabled
1 = Enabled
(1)
See Parameter 304 - [Limit Status] in the PowerFlex 700S drive User Manual for a description of the limit status conditions.