Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 58

Advertising
background image

4-22

Configuring the I/O

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

The new node (‘My_PowerFlex_70_EC_Drive’ in this example) now
appears under the bridge (‘My_ControlNet_Bridge’ in this example) in
the I/O Configuration folder. If you double-click the Controller Tags,
you will see that module-defined data types and tags have been
automatically created (

Figure 4.4

). After you save and download the

configuration, these tags allow you to access the Input and Output data
of the drive via the controller’s ladder logic.

For this example, all Datalinks (A, B, C, and D) are enabled. The Input
Size is set to 12 words and the Output Size is set to 10 words. Also, the
following adapter I/O parameters are set to the following values.

11. Reset the adapter (see

Resetting the Adapter on page 3-7

) or power

cycle the drive.

For the drive speed reference and Datalink parameter values and the
adapter setup parameter values, see

Drive and Adapter Parameter

Settings on page 5-24

.

Figure 4.4

Controller Tags

Save the I/O Configuration to the Controller

After adding the bridge and drive/adapter to the I/O configuration, you must
download the configuration to the controller. You should also save the
configuration as a file on your computer.

Adapter Parameter No.

Setting

13 - [DPI I/O Cfg]

xxxx xxxx xxx1 1111

25 - [M-S Input]

xxxx xxxx xxx1 1111

26 - [M-S Output]

xxxx xxxx xxx1 1111

TIP: When using RSLogix 5000 software, version 16.00 or later, you can
add the I/O configuration of a Generic Profile while the controller is online
and in the Run mode.

Advertising
This manual is related to the following products: