Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 208

Advertising
background image

B-2

Adapter Parameters

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

09

[Reset Module]

No action if set to ‘0’ (Ready). Resets the adapter if
set to ‘1’ (Reset Module). Restores the adapter to
its factory default settings if set to ‘2’ (Set Defaults).
This parameter is a command. It will be reset to ‘0’
(Ready) after the command has been performed.

Default:

0 = Ready

Values:

0 = Ready
1 = Reset Module
2 = Set Defaults

Type:

Read/Write

Reset Required: No

10

[Comm Flt Action]

Sets the action that the adapter and drive will take
if the adapter detects that I/O communication has
been disrupted. This setting is effective only if I/O
that controls the drive is transmitted through the
adapter. When communication is re-established,
the drive will automatically receive commands over
the network again.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

11

[Idle Flt Action]

Sets the action that the adapter and drive will take
if the adapter detects that the controller is in
program mode or faulted. This setting is effective
only if I/O that controls the drive is transmitted
through the adapter. When the controller is put
back in Run mode, the drive will automatically
receive commands over the network again.

Default:

0 = Fault

Values:

0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg

Type:

Read/Write

Reset Required: No

12

[CN Active Cfg]

Displays the source from which the adapter node
address is taken. This will either be ‘0’ (Switches)
or ‘1’ (EEPROM) in which the address from
Parameter 03 - [CN Addr Cfg] is stored. The
source is determined by the settings of the adapter
Node Address switches.

Values:

0 = Switches
1 = EEPROM

Type:

Read Only

Parameter

No.

Name and Description

Details

!

ATTENTION: Risk of injury or equipment damage exists. If the adapter is
transmitting I/O that controls the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting a connected
adapter.

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 10 -
[Comm Flt Action]
lets you determine the action of the adapter and connected
drive if I/O communication is disrupted. By default, this parameter faults the
drive. You can set this parameter so that the drive continues to run, however,
precautions should be taken to verify that the setting of this parameter does not
create a risk of injury or equipment damage. When commissioning the drive,
verify that your system responds correctly to various situations (for example, a
disconnected cable).

!

ATTENTION: Risk of injury or equipment damage exists. Parameter 11 - [Idle
Flt Action]
lets you determine the action of the adapter and connected drive
when the controller is idle. By default, this parameter faults the drive. You can set
this parameter so that the drive continues to run, however, precautions should
be taken to verify that the setting of this parameter does not create a risk of
injury or equipment damage. When commissioning the drive, verify that your
system responds correctly to various situations (for example, a faulted
controller).