Configuring the I/O

4-7

20-COMM-C/Q ControlNet Adapter User Manual

Publication 20COMM-UM003F-EN-P

In this example, Datalinks are used to do the following.

6. In the Module Definition screen, edit the following information.

Read…

Write to…

Output Current (Parameter 3)

Accel Time 1 (Parameter 140)

DC Bus Voltage (Parameter 12)

Decel Time 1 (Parameter 142)

Fault 1 Code (Parameter 243)

High Resolution Reference (Parameter 308)

TIP: To get the latest RSLogix 5000 drive Add-on Profile, go to

http://

www.ab.com/support/abdrives/webupdate

.

Box

Setting

Revision

The major and minor revision of the firmware (database) in the drive. If the
drive’s major and minor revision is not available, the drive database is not
installed on your computer. To get the correct database revision, use one of the
following buttons at the bottom left of the Module Definition screen:
Create Database: Creates a database from an online network drive. Clicking

this button displays an RSLinx software RSWho window. Browse to the
online drive (for this example, PowerFlex 70 EC), select it, and click OK. The
database will be uploaded and stored on the computer. Thereafter, close the
Module Definition screen and then re-open it to display the new revision.

Web Update: When a drive is not available online, opens the Allen-Bradley

Drives Web Updates website to download a specific database file. After
downloading the file, close the Module Definition screen and then re-open it
to display the new revision.

Match Drive: Use this button when the drive being added to the network

matches the drive profile (revision, rating, configuration settings, and so forth)
of an existing online network drive. Click this button to conveniently create a
duplicate drive profile from the online drive, and automatically load this
identical information into the Module Definition screen. This eliminates the
need to manually enter the information each time a new drive with a
matching profile is added to the network.

Electronic
Keying

Compatible Module. The ‘Compatible Module’ setting for Electronic Keying
ensures that the physical module is consistent with the software configuration
before the controller and bridge make a connection. Therefore, ensure that you
have set the correct revision in this screen. See the online Help for additional
information on this and other Electronic Keying settings. If keying is not required,
select ‘Disable Keying’. Drives do not require keying, and so ‘Disable Keying’ is
recommended.