Identity object, Class code, Services – Rockwell Automation 20-COMM-Q ControlNet Adapter User Manual

Page 212: Instances, Class attributes, Instance attributes

Advertising
background image

C-2

ControlNet Objects

20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P

Identity Object

Class Code

Services

Instances

The number of instances depends on the number of components in the
device connected to the adapter. This number of components can be read in
Instance 0, Attribute 2.

Class Attributes

Instance Attributes

Hexadecimal

Decimal

0x01

1

Implemented for:

Service Code

Class

Instance

Service Name

0x01

Yes

Yes

Get_Attributes_All

0x05

Yes

Yes

Reset

0x0E

Yes

Yes

Get_Attribute_Single

Instance

Description

0

Class

1

Host

2…15

Peripherals on Ports 1…14

Attribute ID

Access Rule Name

Data Type

Description

2

Get

Max Instance

WORD

Total number of instances

Attribute ID

Access Rule Name

Data Type

Description

1

Get

Vendor ID

WORD

1 = Allen-Bradley

2

Get

Device Type

WORD

120 (20-COMM-C)
129 (20-COMM-Q)

3

Get

Product Code

WORD

Number identifying product name and rating

4

Get

Revision:

Major
Minor

STRUCT of:

BYTE
BYTE

Value varies
Value varies

5

Get

Status

WORD

Bit 0 = Owned
Bit 2 = Configured
Bit 10 = Recoverable fault
Bit 11 = Unrecoverable fault

6

Get

Serial Number

DWORD

Unique 32-bit number

7

Get

Product Name

SHORT_STRING

Product name and rating

Advertising
This manual is related to the following products: