Publication 20COMM-UM003F-EN-P

Figure 2.3

Mounting and Grounding the Adapter

NOTE: When installing the adapter in a PowerFlex 750-Series drive, see
the 20-750-20COMM and 20-750-20COMM-F1 Communication Carrier
Cards Installation Instructions, publication 750COM-IN001, supplied with
the card.

X1

X2

Drive

Adapter

Internal Interface Cable
folded behind the adapter
and in front of the drive.

PowerFlex 70 - All Frame Sizes

(Adapter mounts in drive.)

Verify metal ground tab is bent 90° and
is under the adapter before tightening
screw. After tightening the screw, verify
continuity exists between the head of
the screw and drive ground.

Ground Tab Detail

PowerFlex 700 Frames 0 and 1

PowerFlex 700S Frames 0 and 1

(Adapter mounts on door.)

PowerFlex 700 Frames 2 and Larger
PowerFlex 700S Frames 2 through 6

(Adapter mounts in drive.)

0.9 N•m

(8.0 lb•in)

4 Places

Verify metal ground tab is bent 90° and
is under the adapter before tightening
screw. After tightening the screw, verify
continuity exists between the head of
the screw and drive ground.

PowerFlex 700H Frames 9 and Larger
PowerFlex 700S Frames 9 and Larger

(Adapter mounts behind HIM panel.)

Ground Tab Detail

0.9 N•m

(8.0 lb•in)

4 Places

0.9 N•m

(8.0 lb•in)

4 Places