Table 13 – Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 100

Advertising
background image

100

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Chapter 5 Using the I/O

Table 13 - Controller Data Table Addresses for PowerFlex 700S Drives with Phase I

Control

Data Table Address Description
N20:1

Logic Status (see

Appendix D

)

N20:2

Speed Feedback LSW

N20:3

Speed Feedback MSW

N20:4

Value of parameter assigned to Parameter 724/725 [Data Out A1] LSW

N20:5

Value of parameter assigned to Parameter 724/725 [Data Out A1] MSW

N20:6

Value of parameter assigned to Parameter 726/727 [Data Out A2] LSW

N20:7

Value of parameter assigned to Parameter 726/727 [Data Out A2] MSW

N20:8

Value of parameter assigned to Parameter 728/729 [Data Out B1] LSW

N20:9

Value of parameter assigned to Parameter 728/729 [Data Out B1] MSW

N20:10

Value of parameter assigned to Parameter 730/731 [Data Out B2] LSW

N20:11

Value of parameter assigned to Parameter 730/731 [Data Out B2] MSW

N20:12

Value of parameter assigned to Parameter 732/733 [Data Out C1] LSW

N20:13

Value of parameter assigned to Parameter 732/733 [Data Out C1] MSW

N20:14

Value of parameter assigned to Parameter 734/735 [Data Out C2] LSW

N20:15

Value of parameter assigned to Parameter 734/735 [Data Out C2] MSW

N20:16

Value of parameter assigned to Parameter 736/737 [Data Out D1] LSW

N20:17

Value of parameter assigned to Parameter 736/737 [Data Out D1] MSW

N20:18

Value of parameter assigned to Parameter 738/739 [Data Out D2] LSW

N20:19

Value of parameter assigned to Parameter 738/739 [Data Out D2] MSW

N20:20

Logic Command (see

Appendix D

)

N20:21

Speed Reference LSW

N20:22

Speed Reference MSW

N20:23

Value of parameter assigned to Parameter 707/708 [Data In A1] LSW

N20:24

Value of parameter assigned to Parameter 707/708 [Data In A1] MSW

N20:25

Value of parameter assigned to Parameter 709/710 [Data In A2] LSW

N20:26

Value of parameter assigned to Parameter 709/710 [Data In A2] MSW

N20:27

Value of parameter assigned to Parameter 711/712 [Data In B1] LSW

N20:28

Value of parameter assigned to Parameter 711/712 [Data In B1] MSW

N20:29

Value of parameter assigned to Parameter 713/714 [Data In B2] LSW

N20:30

Value of parameter assigned to Parameter 713/714 [Data In B2] MSW

N20:31

Value of parameter assigned to Parameter 715/716 [Data In C1] LSW

N20:32

Value of parameter assigned to Parameter 715/716 [Data In C1] MSW

N20:33

Value of parameter assigned to Parameter 717/718 [Data In C2] LSW

N20:34

Value of parameter assigned to Parameter 717/718 [Data In C2] MSW

N20:35

Value of parameter assigned to Parameter 719/720 [Data In D1] LSW

N20:36

Value of parameter assigned to Parameter 719/720 [Data In D1] MSW

N20:37

Value of parameter assigned to Parameter 721/722 [Data In D2] LSW

N20:38

Value of parameter assigned to Parameter 721/722 [Data In D2] MSW