199

EtherNet/IP Objects Appendix C

Class Attributes

0x6800…0x6BFF

(1)

26624…27647

DPI Port 10

0x6C00…0x6FFF

(1)

27648…28671

DPI Port 11

0x7000…0x73FF

(1)

28672…29695

DPI Port 12

0x7400…0x77FF

(1)

29696…30719

DPI Port 13

0x7800…0x7BFF

(1)

30720…31743

DPI Port 14

(1) These instances are supported only when the adapter is used with a PowerFlex 750-Series drive.

Instances (Hex.)

(Dec.)

Device

Example

Description

Attribute ID

Access Rule

Name

Data Type

Description

0

Get

Number of Instances

WORD

Number of parameters in the device

1

Set

Write Protect Password

WORD

0 = Password disabled
n = Password

2

Set

NVS Command Write

BYTE

0 = No Operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory

3

Get

NVS Parameter Value Checksum

WORD

Checksum of all parameter values in a user set in NVS

4

Get

NVS Link Value Checksum

WORD

Checksum of parameter links in a user set in NVS

5

Get

First Accessible Parameter

WORD

First parameter available if parameters are protected by passwords.
A ‘0’ indicates all parameters are protected.

7

Get

Class Revision

WORD

2 = DPI

8

Get

First Parameter Processing Error

WORD

The first parameter that has been written with a value outside of its
range. A ‘0’ indicates no errors.

9

Set

Link Command

BYTE

0 = No Operation
1 = Clear All Parameter Links (This does not clear links to function
blocks.)