Figure 18 – Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 76

Advertising
background image

76

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Chapter 4 Configuring the I/O

Figure 18 - MicroLogix 1100/1400 Message Configuration Screens for the Logic

Command, Reference, and Datalink In

General Tab BoxSetting
This Controller (data for MicroLogix 1100)
Channel

1 (integral). Controller port to which the network is connected.

Communication Command

500CPU Write. The controller type and command type for the controller to read or write data.

Because the MicroLogix 1100 is part of the SLC-500 controller family, the ‘500CPU’ controller

type was selected. The ‘Write’ command type was selected to write data to the drive.

Data Table Address

(1)

N20:20. An unused controller data table address containing the data to be written to the drive.

Size in Elements

(2)

19. Number of elements (words) to be transferred. Each element size is a 16-bit integer.

Target Device (data for adapter/drive)
Message Timeout

5. Message timeout duration in seconds.

Data Table Address

(3)

N41:0. Specific starting address of the destination file in the drive.

Routing Information File

RI9:2. An unused routing information file for the controller.

MultiHop Tab BoxSetting
To Address

10.91.100.79. The IP address of the adapter connected to the drive.

(1) For details on data table addresses for this example project, see

Table 11

Table 14

starting on

page 98

.

(2) For details to determine element size for a specific drive, see

Understanding Controller Data Table Addresses on page 97

.

(3) For N-File details, see

N-Files on page 192

.

TIP

This message will error out if the Control Timeout value is not changed from a non-

zero value. Refer to

page 71

for writing a value to the Control Timeout.

TIP

If the controller is controlling more than one drive, it is recommended to

intersperse the control I/O messaging for each drive to conserve network

bandwidth and decrease response time. That is, sequence the message

instructions for each drive so that its group of messages will occur at a different

time than those for another drive.