Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Appendix B Adapter Parameters

44

45

46

47

[Peer Inp Addr 1]

[Peer Inp Addr 2]

[Peer Inp Addr 3]

[Peer Inp Addr 4]
Sets the IP address bytes that specifies the device

from which the adapter receives (consumes) peer

I/O data.

Important: The Peer Inp Addr must be on the

same subnet as the 20-COMM-ER. See

page 226

for more information.
Changes to these parameters are ignored when

Parameter 49 - [Peer Inp Enable] is set to ‘1’

(On).

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

255

Type:

Read/Write

Reset Required: No

48

[Peer Inp Timeout]
Sets the timeout for a peer I/O connection. If the

time is reached without the adapter receiving

(consuming) a message, the adapter will respond

with the action specified in Parameter 43 - [Peer

Flt Action].
In an adapter receiving (consuming) peer I/O, the

value of this parameter must be greater than the

product of the value of Parameter 54 - [Peer Out

Time] in the adapter transmitting (producing) peer

I/O multiplied by the value of Parameter 55 - [Peer

Out Skip] in the adapter transmitting (producing)

peer I/O.

Default:

10.00 Seconds

Minimum:

0.01 Seconds

Maximum:

10.00 Seconds

Type:

Read/Write

Reset Required: No

49

[Peer Inp Enable]
Determines if peer I/O input is on or off.

Default:

0 = Off

Values:

0 = Off

1 = On

Type:

Read/Write

Reset Required: No

50

[Peer Inp Status]
Displays the status of the consumed peer I/O input

connection.

Default:

0 = Off

Values:

0 = Off

1 = Waiting

2 = Running

3 = Faulted

Type:

Read Only

Parameter
No. Name and Description

Details

255 . 255 . 255 . 255

[Peer Inp Addr 1]

[Peer Inp Addr 2]

[Peer Inp Addr 3]

[Peer Inp Addr 4]