Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Appendix B Adapter Parameters

29

30

31

32

33

34

35

36

[Flt Cfg A1 In]

[Flt Cfg A2 In]

[Flt Cfg B1 In]

[Flt Cfg B2 In]

[Flt Cfg C1 In]

[Flt Cfg C2 In]

[Flt Cfg D1 In]

[Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the

drive if any of the following is true:

·

Parameter 23 - [Comm Flt Action] is set to ‘4’

(Send Flt Cfg) and I/O communication is

disrupted.

·

Parameter 24 - [Idle Flt Action] is set to ‘4’

(Send Flt Cfg) and the controller is idle.

·

Parameter 43 - [Peer Flt Action] is set to ‘4’

(Send Flt Cfg) and peer I/O communication is

disrupted.

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

4294967295

Type:

Read/Write

Reset Required: No

Important: If the drive uses 16-bit

Datalinks, the most significant word of

this value must be set to zero (0) or a

fault will occur.

37

[M-S Input]
Sets the Master-Slave input data. This data is

produced by the scanner and consumed by the

adapter.

Default:

xxx0 0001

Bit Values:

0 = I/O disabled

1 = I/O enabled

Type:

Read/Write

Reset Required: Yes

38

[M-S Output]
Sets the Master-Slave output data. This data is

produced by the adapter and consumed by the

Master device (for example, scanner).

Default:

xxx0 0001

Bit Values:

0 = I/O disabled

1 = I/O enabled

Type:

Read/Write

Reset Required: Yes

39

[Ref Adjust]
Sets the percent scale factor for the Reference

received from the network.

Default:

100.00%

Minimum:

0.00%

Maximum:

200.00%

Type:

Read/Write

Reset Required: No

Parameter
No. Name and Description

Details

Bit

Definition

Not

Used

Not

Used

Not

Used

Dat

alink

D I

nput

Dat

alink

C I

nput

Dat

alink

B I

nput

Dat

alink

A I

nput

Cm

d/Ref

Default

x

x

x

0 0 0 0 1

Bit

7 6 5 4 3 2 1 0

Bit

Definition

Not

Used

Not

Used

Not

Used

Dat

alink

D Ou

tput

Dat

alink

C Ou

tput

Dat

alink

B

Out

put

Dat

alink

A

Out

put

Cm

d/Ref

Default

x

x

x

0 0 0 0 1

Bit

7 6 5 4 3 2 1 0

ATTENTION: To guard against equipment damage and/or personal injury, note

that changes to Parameter 39 - [Ref Adjust] take effect immediately. A drive

receiving its Reference from the adapter will receive the newly scaled

Reference, resulting in a change of speed.