Configuring the I/O Chapter 4

Create MicroLogix 1100/1400 Ladder Logic for the Logic Command,

Reference, and Datalink In

1.

Insert another separate rung.

2.

Double-click on the rung to display the rung editor.

3.

Enter MSG MGxx:n, where:

xx is an unused data file number (for example, MG12:n), and

n is an unused element of the data file chosen for xx (for example, MG12:0)

4.

Press Enter.

5.

Insert another separate rung.

6.

Double-click on the rung to display the rung editor.

7.

Enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ER BND OTU
MGxx:n/EN

, where:

xx and n must correspond to the assigned data file number and element

(for example, MG12:0) for the message created in steps 1…4.

Important: The information must be entered with appropriate numbers

for ‘xx’ and ‘n’ for your application, and with spaces and
forward slashes exactly as shown.

8.

Press Enter.

9.

In the MSG instruction (

Figure 17

), double-click Setup Screen to launch

the message configuration screen (

Figure 18

).

Figure 17 - MicroLogix 1100/1400 Ladder Logic for the Logic Command, Reference,

and Datalink In

10.

Configure the General tab fields by entering or verifying the information
shown in the message configuration screen.

Steps 1…4

Steps 5…8

Step 9