Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual
Page 31

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
31
Configuring the Adapter Chapter 3
6.
In the BOOTP Request History list, either double-click the adapter’s
Ethernet Address (MAC) noted in Step 1, or click New in the Relation
List.
The New Entry dialog box appears.
In the first case, the Ethernet Address (MAC) is automatically entered. In
the latter case, you must manually enter it.
7.
Edit the following:
8.
Click OK to apply the settings.
The adapter appears in the Relation List with the new settings.
9.
To assign this configuration to the adapter permanently, select the device
in the Relation List and click Disable BOOTP/DHCP.
When power is cycled on the adapter, it will use the configuration you
assigned it and not issue new BOOTP requests.
Box
Type
IP Address
A unique IP address for the adapter
Host Name
Optional
Description
Optional
TIP
To enable BOOTP for an adapter that has had BOOTP disabled, first select the
adapter in the Relation List, then click Enable BOOTP, and lastly reset the adapter
or power cycle the drive.