Instance attributes – Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 200

Advertising
background image

200

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Appendix C EtherNet/IP Objects

Instance Attributes

Attribute ID

Access Rule

Name

Data Type

Description

6

Get

DPI Offline Read Full

STRUCT of:

BOOL[32]
CONTAINER
CONTAINER
CONTAINER
STRING[16]
STRING[4]
WORD
WORD
WORD
WORD
WORD
WORD
WORD
BYTE
BYTE
WORD
WORD
CONTAINER
WORD
WORD
WORD
INT

Descriptor
Offline minimum value
Offline maximum value
Offline default value
Parameter name
Offline parameter units
Online minimum parameter instance
Online maximum parameter instance
Online default parameter instance
Multiple parameter instance
Divisor parameter instance
Base parameter instance
Offset parameter instance
Formula number
Pad byte (always zero)
Help instance
Pad word (always a value of zero)
Parameter value
Multiplier
Divisor
Base
Offset

7

Get

DPI Online Read Full

STRUCT of:

BOOL[32]
CONTAINER

(1)

CONTAINER
CONTAINER
CONTAINER
WORD
WORD
STRING[4]
WORD
WORD
WORD
INT
BYTE[3]
BYTE
STRING[16]

Descriptor (see page

202

)

Parameter value
Minimum value
Maximum value
Default value
Next parameter
Previous parameter
Units (for example, Amp, Hz)
Multiplier

(2)

Divisor

(2)

Base

(2)

Offset

(2)

Link (source of the value) (0 = no link)
Always zero (0)
Parameter name

8

Get

DPI Descriptor

BOOL[32]

Descriptor (see page

202

)

9

Get/Set

DPI Parameter Value

Various

Parameter value in NVS.

(3)

10

Get/Set

DPI RAM Parameter Value

Various

Parameter value in temporary memory. Valid only
for DPI drives.

11

Get/Set

DPI Link

BYTE[3]

Link (parameter or function block that is the source
of the value) (0 = no link)

12

Get

Help Object Instance

WORD

ID for help text for this parameter

13

Get

DPI Read Basic

STRUCT of:

BOOL[32]
CONTAINER
CONTAINER
CONTAINER
CONTAINER
STRING[16]
STRING[4]

Descriptor (see page

202

)

Parameter value
Minimum value
Maximum value
Default value
Parameter name
Units (for example, Amp, Hz)

14

Get

DPI Parameter Name

STRING[16]

Parameter name

15

Get

DPI Parameter Alias

STRING[16]

Customer supplied parameter name.

16

Get

Parameter Processing Error

BYTE

0 = No error
1 = Value is less than the minimum
2 = Value is greater than the maximum

Advertising