Using Explicit Messaging Chapter 6

ControlLogix Controller Example Scattered Write Response Data

The results of the message appear in the destination tag named
Scattered_Write_Response (

Figure 46

). Values of ‘0’ indicate no errors occurred.

Figure 46 - Example Scattered Write Response Data for PowerFlex 7-Class Drive

ControlLogix Controller – Explanation of Request and Response Data for

Read/Write Multiple Messaging, RSLogix 5000 Software, All Versions

The data structures in

Figure 47

and

Figure 48

use 16-bit words and can

accommodate up to 22 parameters in a single message. In the Response Message, a
parameter number with the high bit set indicates that the associated parameter
value field contains an error code (parameter number in response data will be
negative).

Important: See

Table 17 on page 106

for limitations of PowerFlex 7-Class

drives when using Class code 0x93 for explicit messaging.